Performance Data - TCG 2020 / TCG 2020 K / TCG 2020 K1

Natural gas applications, NOx ≤ 500 mg/Nm3 *

TCG 2020 V12RW = Optimized for high total efficiency at requested power TCG 2020 V12 K1KW = Optimized for robustness and low CAPEX at requested power
Engine type 50 Hz 50 Hz
Electrical output kW 1000 1000
Thermal output ± 8% kW 1056 1191
Electrical efficiency % 43.0 40.0
Thermal efficiency % 45.4 47.6
Total efficiency % 88.4 87.6
Power to heat ratio ** 0.95 0.84
TCG 2020 V12 KK = Optimized for robustness and low CAPEX TCG 2020 V12R = Optimized for high total efficiency
Engine type 50 Hz 60 Hz 50 Hz 60 Hz
Electrical output kW 1125 1125 1200 1200
Thermal output ± 8% kW 1251 1262 1189 1196
Electrical efficiency % 41.0 40.7 43.7 43.4
Thermal efficiency % 45.6 45.6 43.3 43.2
Total efficiency % 86.6 86.3 87.0 86.6
Power to heat ratio ** 0.90 0.90 1.00 1.00
TCG 2020 V16 KK = Optimized for robustness and low CAPEX TCG 2020 V16R = Optimized for high total efficiency
Engine type 50 Hz 60 Hz 50 Hz 60 Hz
Electrical output kW 1500 1500 1560 1560
Thermal output ± 8% kW 1675 1686 1576 1589
Electrical efficiency % 40.9 40.6 43.3 43.0
Thermal efficiency % 45.7 45.7 43.8 43.8
Total efficiency % 86.6 86.3 87.1 86.8
Power to heat ratio ** 0.89 0.89 0.99 0.98
TCG 2020 V20R = Optimized for high total efficiency TCG 2020 V20 (HE)P = Optimized for high electrical efficiency
Engine type 50 Hz 60 Hz 50 Hz
Electrical output kW 2000 2000 2000
Thermal output ± 8% kW 1983 1997 1912
Electrical efficiency % 43.7 43.4 44.4
Thermal efficiency % 43.3 43.3 42.5
Total efficiency % 87.0 86.7 86.9
Power to heat ratio ** 1.00 1.00 1.04

Biogas, landfill gas, and sewage gas applications, NOx ≤ 500 mg/Nm3 *

TCG 2020 V12XW = Optimized for operation with biogases at requested power TCG 2020 V12X = Optimized for operation with biogases
Engine type 50 Hz 50 Hz 60 Hz
Electrical output kW 1000 1200 1200
Thermal output ± 8% kW 1035 1192 1201
Electrical efficiency % 42.6 43.0 42.7
Thermal efficiency % 44.1 42.7 42.7
Total efficiency % 86.7 85.7 85.4
Power to heat ratio ** 0.97 1.00 1.00
TCG 2020 V16X = Optimized for operation with biogases TCG 2020 V20X = Optimized for operation with biogases
Engine type 50 Hz 60 Hz 50 Hz 60 Hz
Electrical output kW 1560 1560 2000 2000
Thermal output ± 8% kW 1566 1580 2010 2024
Electrical efficiency % 42.7 42.3 43.0 42.7
Thermal efficiency % 42.9 42.8 43.2 43.2
Total efficiency % 85.6 85.1 86.2 85.9
Power to heat ratio ** 1.00 0.99 1.00 0.99

* With 5% O2 and dry exhaust gas

** The power to heat ratio is calculated by dividing the electrical efficiency by the thermal efficiency. Please remember that this is a theoretical value that may deviate from actually measured values.

CHP ROI Calculator

Gas engines & Products

Cogeneration Power Plant Solutions

Eco-friendly MWM cogeneration power plants with combined heat and power enable decentralized, economical and energy-efficient power production.

Container Cogeneration Plant

Container Cogeneration Plant, the mobile power plant of MWM. Complete turnkey systems for special applications. Quality "made in Germany". Optimized for reliable, smooth operation and fast service.

Gas Engine TCG 3016

400 - 1,000 kWel

New development – greatly reduced operating and installation costs and fully digitized power plant control.

Gas engine TCG 2032

3,000 - 4,500 kWel

High availability, low installation costs. All gas types: natural gas, biogas, landfill gas, sewage gas, mine gas, coke oven gas. Mainly used in large IPP projects with up to 100 MWel.

Contact

MWM Representation in Moscow
Sales & Service
Caterpillar Energy Solutions GmbH
Bldg. 1, 5/2, 1st Kazachiy per.
119017 Moscow
Russian Federation

T: +7 495 234 49 41
E: A00BAaCA9cBDA64BEA9FA6G4B-BA09fC6DGA0a9EaB6BeA56FaF7BGeEeD5Cb
W: www.mwm.com.ru